SF6 decomposition product tester, by monitoring SO2, H2S and CO three decomposition products at the same time, can quickly detect and judge the early failure of SF6 electrical equipment (circuit breaker, transformer, transformer, GIS and bushing, etc.) on site.
This instrument can be widely used in SF6 electrical equipment in electric power, railway, metallurgy and petrochemical industries.
1. Minimum detection amount: 0.1ppm
2. Stability: when the temperature changes from 20°C to 40°C, the maximum zero drift is ≤±0.1ppm
3. Accuracy: When the measurement is less than or equal to 2ppm, the error is less than or equal to ±0.1ppm
When measuring >2ppm, the error is less than or equal to ±0.2ppm
4. Measuring range: SO2: 0~100μL/L
H2S: 0~100μL/L
CO: 0~1000μL/L
5. Measurement tolerance: SO2≤10μL/L, ±1μL/L; SO2>10μL/L, ±10%,
H2S≤10μL/L,±1μL/L; H2S>10μL/L,±10%
CO≤50μL/L,±4μL/L;CO>50μL/L,±8%
6. Repeatability: SO2≤10μL/L,±0.5μL/L; SO2>10μL/L,±5%,
H2S≤10μL/L,±0.5μL/L; H2S>10μL/L,±5%
CO≤50μL/L,±2μL/L;CO>50μL/L,±4%
7. Resolution: SO2≤0.1μL/L, H2S≤0.1μL/L, CO≤1μL/L
8. Response time: the maximum shall not exceed 5min.
9. Pressure: The pressure of the instrument pipeline is not less than 1MPa.
10. Temperature range: -40℃~+50℃
11. Humidity range: ≤95%RH
12. Atmospheric pressure: 86kPa~106kPa
13. Self-provided power supply: built-in rechargeable battery, which can work continuously for more than 10 hours after being fully charged
14. Appearance: 252×310×98mm
15. Weight: 2.5kG
16. Communication: RS232
Email:info@wgdchipot.com
Whatsapp: +86 13657267902
Skype: sallyliao2006
Wechat:sallyliao ( 13657267902)
Tel:+86 13657267902
Address:13 / F, Building 2, Hangang Science and Technology Industrial Park, Jintan Road, Wuhan, Hubei, China.