According to the characteristics of the outer sheath fault, this instrument uses the voltage drop method to initially measure the ground fault of the cable outer sheath, and then uses the step voltage method to accurately find the fault point. The instrument is used for fault detection of outer sheath of cross-linked cables; it can also be used for fault detection of buried wires and all-plastic wires (cables without metal sheath); it can also be used for 15KV DC withstand voltage test of cables or other electrical appliances.
1. transmitter
Power supply: AC220V±10% 50HZ;
Input power: 1000W
Display mode: 5.6 inch LCD screen
Output voltage: DC 0---15KV negative polarity high voltage; continuously adjustable.
Working mode: DC, withstand voltage, pulse,
Maximum output current: 1A. It can work continuously in short circuit.
Withstand voltage gear: 0---15KV negative polarity high voltage; maximum current: 1000μA
Dimension: 450mm×330mm×350mm
Weight: 20Kg
2. receiver
Display mode: color LCD display
Display range: 50-0-50 (wider display range and higher resolution)
Sensitivity: 0.10mV
Power supply: 6×1.5V
Dimension: 120mm×120mm×230mm
Weight: 1Kg
Email:info@wgdchipot.com
Whatsapp: +86 13657267902
Skype: sallyliao2006